QuantaDat/nSens
QuantaDat/nSens
Multi-sensor measurement system for professional climatic controls
Description
QuantaDat / nSens multi-sensor system
This measuring system consists of transmitter and sensor, whereby several of the latter can be connected simultaneously and therefore save on costs per measurement point. The QuantaDat has a big graphic display, 4 measurement channels and 4 analogue signal outputs.
The digital nSens probe measures with high accuracy, linear response and can be calibrated at 13 humidity- and 2 temperature points with the nSoft-CAL software. The calibration data are stored on the sensor.
This absolutely unique field measuring device combines modern electronics and software with versatility and flexibility.
Novasina's multi-sensor technology reduces costs per measuring point and the humidity measuring technology guarantees an accurate measurement with optimal response characteristics over the full measurement range. In addition the intelligent sensor with stored calibration data allows a fast and simple replacement without necessity for a subsequent system recalibration.
The cable length between transmitter and sensor is variable and can be extended up to 30m. Various hard- and software features such as cable fixing, sensor plug-in system, adjustable analogue output, automatic sensor identification, calibration software etc. complete this system.
Recommended accessories are the reusable Novasina SAL-SC humidity generators, which are also available with accredited traceable calibration certificate.
Range of use
The industrial and robust design make these measurement devices suitable for almost all applications in the world of state-of-the-art measurement technology.
Features and Benefits
- Multi-sensor -> reduced costs per measurement point
- Integrated climatic parameter processor
- 4 freely configurable analogue outputs
- Easy installation, set-up and service
- Digital sensor with calibration data storage
- High measuring accuracy and linear response
- Fast and safe replaceable with plug-in system
- Variable cable length up to 30m available
Applications
- Clean Room technology (pharmaceutical-, chemical-, semiconductor-industry, hospitals)
- Chemical- and painting processes
- Paper- and textile industry
- Laboratories, calibration rooms
- Climatic chambers, green houses, meteorological-stations
- Combustion processes, power plants
- OEM solutions
Measuruement data
Humidity measurement | |
Measurement range: | 0...100%RH |
resistive-electrolytic sensor: | |
Accuracy | typ. +/- 0.5%RH (15...30°C) |
typ. +/- 0.8%RH (0...50°C) | |
typ. +/- 2.5%RH (-20...+80°C) | |
Temperature measurement | |
Measurement range: | -20...80°C |
Accuracy | typ. +/-0.1K (0...+70°C) |
typ. +/-0.2K (-20...+80°C) | |
Suitable calibration | Sensor Checks SAL-SC |
standards: | 6/11/33/53/75/90/97%RH |
Technical data
Power supply | 24V +/- 15% AC or DC (galvanic isolated) |
Power consumption | max. ca.3W |
Display | Graphical display with LED backlight, 128 x 64 Pixel |
Selectable parameters |
Humidity; Temperature; Mixing ratio; Water vapour partial pressure; Dew-point temperature; Specific enthalpy; Absolute humidity |
Analogue outputs | 4 scalable & adjustable analogue outputs, 0/4..20mA or 0/2..10V |
Digital outputs | RS-485 Version with relay: 2 relay contacts, switching power <=50V/2A/60W |
Housing material | ABS - lid blue RAL 5014, bottom grey RAL 7035 |
Protection class | IP54 |
Operating temperature | 0 to 50°C |
Storage temperature | -10 to +60° C (non-condensing) |
CE-/EMC compatibility |
Safety: IEC 61010-1:2010 EMC: IEC 61000-6-2:2005, EN 61000-6-2:2005 IEC 61000-6-3:2006+A1:2010, EN 61000-6-3:2007+A1:2011 |